Building Wires & Cables  |  Power & Control system  |  High'n Medium Voltage  |  Bare Conductor  |  Special Cable & Others


  VTA-TIS

0.6/1(1.2)kV 90 0C XLPE Insulated PVC Jacketed Flame Retardant Power Cable
SCOPE:
This specification covers
Lead Free PVC plastic electrical insulation tape
to be used in electrical
service at temperature 0 ~80oC.
The tape shall be used for insulation
of jointed splices of cables and wires.
The tape must have good insulation
properties, heat, weather, flame
resistance, and lead free materials
for environment, suitable for tropical
country.
STANDARD:

The lead Free PVC plastic electrical insulation tape shall be manufactured
and tested in accordance with
TIS 386-2531:

Dimension
1) Thickness (mm) 0.125,0.18 + 0.025
2) Width (mm) 19 + 1.0
3) Length (m)  10 + 1.0
                             - 0

  FI-0.6/1KV-CV

0.6/1(1.2)kV 90 0C XLPE Insulated PVC Jacketed Flame Retardant Power Cable
CABLE STRUCTURE
NUMBER OF CORE :
1 up to 4 core
CONDUCTOR : Concentric stranded and
:compact stranded annealed Copper
sizes 1.5 mm2 up to 1000 mm2
INSULATION : Cross –linked Polyethylene ( XLPE )
Color: Natural(Translucent )
Core identification : Compound-color Black, White, Red, Green or Color tape
SHEATH : Flame Retardant PVC
Color : Black
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not exceeding 1 kv
TESTING VOLTAGE : 3.5 kv
REFERENCE : : IEC 60502-1
FLAME RETARDANT STANDARD : IEEE 383
  FD-0.6/1KV-CV

0.6/1(1.2)kV 90 0C XLPE Insulated PVC Jacketed Flame retardant Power cable
CABLE STRUCTURE
NUMBER OF CORE :
1 up to 4 core
CONDUCTOR : Concentric stranded
and compact stranded anneaded copper, size 1.5 mm2 up to 1000 mm2
INSULATION :
Cross- link Polyethylene ( XLPE )
Color : Natural ( Translucent )
Core identification : Compound-color Black ,White ,
Red, Green or tape
SHEATH : Flame Retardant PVC
CLASSIFICATION : Maximum conductor temperature 90 °C ,Circuit
Voltage not exceeding 1 kV
TESTING VOLTAGE : 3.5 kv
REFERENCE : : IEC 60502-1
FLAME RETARDANT STANDARD : 60332-3 Cat.C


  FRLH-IE

450/750 V 90 0C XLPE Insulated Flame Retardant with Low Smoke and Zero Halogen For Electric Wire and Cable
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Concentric stranded
Concentric stranded and compact stranded anneaded copper, Size 1.5 mm2 up to 630 mm2
INSULATION : Low Smoke and zero halogen cross-linked polyethylene
( LSOH-XLPE)
Color : 1.5 mm2 to 10 mm2 : any colour
16 mm2 to 630 mm2 : black
SHEATH : Flame Retardant PVC
CLASSIFICATION : Maximum conductor temperature 90 °C ,Circuit
voltage and exceeding 750 V
TESTING VOLTAGE : 2.5 kv
REFERENCE STANDARD : BS7211
SMOKE DENSITY TEST : BS EN 50268-2 ( IEC 61034-2)
ACID GAS TEST : BS EN 50267-2 -2
( IEC 60754-2 )
FLAME RETARDANT STANDARD : BS 4066 part 1

 

  FDLH-0.6/1KV-CE-SWA

0.6/1(1.2)kV 90 0C XLPE Insulated PE Jackets Steel Wire Armored Flame Retardant with Low Smoke and Zero Halogen Power Cable
CABLE STRUCTURE
NUMBER OF CORE :
2 up to 4 core
CONDUCTOR : Concentric strand and
compact stranded annealed copper,
Sizes 1.5 mm2 up to 400 mm2
INSULATION :
Low Smoke and zero halogen cross-linked polyethylene
( LSOH-XLPE)
Color : Natural ( Translucent )
Core identification : Compound –color Red, Yellow, Blue , Black
ARMOR : Steel wire armour
SHEATH : Low smoke and zero halogen polyethylene ( LSOH-PE)
Color : Black
CLASSIFICATION : Maximum conductor temperature 90 0C , Circuit voltage not
Exceeding 1 kV
TESTING VOLTAGE : 3.5 kV
REFERENCE STANDARD : BS 6724
SMOKE DENSITY TEST : BS EN 50268-2 ( IEC 61034-2)
ACID GAS TEST : BS EN 50267-2-2 ( IEC 60754-2)
FLAME RETARDANT STANDARD : BS 4066 part 3 Cat C

  FS/FDLH-0.6/1KV-XLPE ( C )

0.6/1(1.2)kV Mica Fire-barrier Copper Conductor 90 0C XLPE Insulated Fire Resistant and Retardant with Low Smoke and Zero Halogen Cable
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Concentric stranded and
and compact stranded annealed copper Size 1.5 mm2 up to 400 mm2
INSULATION :
Low smoke and zero halogen cross-linked polyethylene
( LSOH-XLPE )
CLASSIFICATION : Maximum conductor temperature 90 0C ,Circuit voltage not exceeding 1 kV
TESTING VOLTAGE : 2.5 kV
REFERENCE STANDARD : Based on BS 7211
SMOKE DENSITY TEST : BS EN 50268-2 ( IEC 61034-2)
ACID GAS TEST : BS 6383 Cat. CWZ
FLAME RETARDANT STANDARD : BS 4066 part 1


  FS/FDLH-0.6/1KV-CE-SWA

0.6/1(1.2)kV Mica Fire-Barrier Copper Conductor 90 0C XLPE Insulated PE Jacketed Steel Wire Armored Fire Resistant and Flame Retardant with Low Smoke and Zero Halogen Power Cable
CABLE STRUCTURE
NUMBER OF CORE :
2 up to 4 core
CONDUCTOR :
Concentric stranded and
compact stranded annealed
copper, Sizes 1.5 mm2 up to 400 mm2
INSULATION : Low Smoke and zero halogen cross-linked polyethylene
( LSOH-XLPE )
Color : Red, Yellow, Blue, Black
ARMOUR : Steel wire armor
SHEATH : Low Smoke and zero halogen polyethylene ( LSOH-PE )
CLASSIFICATION : Maximum conductor temperature 90 0C ,Circuit voltage not
Exceeding 1kV
TESTING VOLTAGE : 3.5 kV
REFERENCE : BS 7846
SMOKE DENSITY : BS EN 50268-2 ( IEC 61034-2)
ACID GAS TEST : BS EN 50267-2-2 ( IEC 60754-2)
FLAME RETARDANT STANDARD : BS 6387 Cat. CWZ . , BS 4066 part 3 Cat C

  YAZAKI KINE LINE TAPE

Ride of the Problem!!
with drawing beautiful line
Convenient, Clear and Suitable for Temporary Work

- Manufactured by Thai-Yazaki Electric Wire Co.,Ltd
- Use easily
- Can attach to various types of smooth floor
- Easy to remove when needless
- Good for 5S activities
- Bright color shades
- Mild for environment (Lead Free)

Application :
YAZAKI LINE TAPE is especially designed for drawing line.
It is suitable for temporary work, layout line of area, walkline in factory, 5s etc.

How to use YAZAKI LINE TAPE :
1. Clean surface and stick YAZAKI LINE TAPE on the floor
2. In case of remove, pull YAZAKI LINE TAPE at a right angle slowly.

Notice :
1.) Avoid using in heavy loading area
2.) Do not use for electric insulation purpose
3.) Not suitable for wet, dirty or oily surface


  STAINLESS TAPED CABLE

300 V 70 °C PVC INSULATED AND SHEATHED ROUND TYPE
For 40 years, we have researched and developed many type of cable to serve you.
Today, THAI-YAZAKI ELECTRIC WIRE CO.,LTD. would like to recommend the new product,
STAINLESS TAPED CABLE
- O.D. smaller
- Flexible but strong
- Anti rust
- Anti rat
- Saving cost

Comparision between STAINLESS TAPED CABLE and Conventional Steel Wire Armored Cable