Building Wires & Cables  |  Power & Control system  |  High'n Medium Voltage  |  Bare Conductor  |  Special Cable & Others


  1.8 /3(3.6) KV-CV

1.8/3 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE : Single and 3 cores
CONDUCTOR : Compact round stranded
annealed copper, Sizes. 10 mm2 up to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color: Natural (Translucent)
Core identification: Color tape White, Red and Blue
SHEATH : PVC Color: Black
SHIELD : Copper tape, thickness 0.1mm
CLASSIFICATION : Maximum conductor temperature 90 °C
Circuit voltage not exceeding 3,600 volts
TESTING VOLTAGE : 6,500 volts
REFERENCE : IEC 60502-1

                                            < Click View To Price >
  3.6 /6(7.2) KV-CV

3.6/6 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single and 3 cores
CONDUCTOR :
Compact round stranded annealed copper, Sizes. 10 mm2 up to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color: Natural (Translucent)
Core identification: Color tape White,Red and Blue
SHEATH : PVC Color: Black
SHIELD : Copper tape, thickness 0.1mm
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not exceeding 7,200 volts
TESTING VOLTAGE : 12,500 volts
REFERENCE : IEC 60502-2

                                            < Click View To Price >


   6 /10(12) KV-CV

6/10 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single and 3 cores
CONDUCTOR :
Compact round stranded
annealed copper, Sizes. 16 mm2 up
to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color: Natural (Translucent)
Core identification: Color tape White,Red and Blue
SHEATH : PVC Color: Black
SHIELD : Copper tape, thickness 0.1mm
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not
exceeding 12,000 volts
TESTING VOLTAGE : 21,000 volts
REFERENCE : IEC 60502-2


  8.7/15(17.5) KV-CV

8.7/15 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED
POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE : Single and 3 cores
CONDUCTOR :
Compact round stranded annealed copper, Sizes. 25 mm2 up to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color : Natural (Translucent)
Core identification: Color tape White, Red and Blue
SHEATH : PVC Color : Black
SHIELD : Copper tape, thickness 0.1mm
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not
exceeding 17,500 volts
TESTING VOLTAGE : 30,500 volts
REFERENCE : IEC 60502-2
  12/20(24) KV-CV

12/20 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER
CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single and 3 cores
CONDUCTOR : Compact round stranded
annealed copper, Sizes. 35 mm2 up to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color : Natural (Translucent)
Core identification: Color tape White,Red and Blue
SHEATH : PVC Color : Black
SHIELD : Copper tape, thickness 0.1mm
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not
exceeding 24,000 volts
TESTING VOLTAGE : 48,000 volts
REFERENCE : IEC 60502-2
  24 KV- OC

CROSS – LINKED POLYETHYLENE PARTIAL INSULATED ALL ALUMINIUM CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Compact round stranded
hard drawn aluminum conductor,
Sizes 35 mm2 up to 185 mm2
INSULATION :
Cross-linked polyethylene (XLPE) Color: Black
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not
exceeding 24,000 volts
TESTING VOLTAGE : 11,000 volts
REFERENCE : ICEA S-66-524


  15 KV-CC

ALL ALUMINIUM SPACED AERIAL CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Compact round stranded
hard drawn
Aluminum conductors, Sizes 35 mm2 up
to 240 mm2
INSULATION :
Cross-linked polyethylene (XLPE) Color : Natural
SHEATH : Cross-linked polyethylene (XLPE) Color : Black
CLASSIFICATION : Maximum conductor temperature 90 °C Circuit voltage not
exceeding 15,000 volts
TESTING VOLTAGE : 27,000 volts
REFERENCE : ICEA S-66-524
  33 KV- OC

CROSS – LINKED POLYETHYLENE PARTIAL INSULATED ALL ALUMINIUM CABLE
CABLE STRUCTURE
NUMBER OF CORE : Single Core
CONDUCTOR : Compact round stranded
hard drawn aluminium wires,
Sizes. 35 mm2 up to 185 mm2
INSULATION :
Cross-linked polyethylene (XLPE) Color: Black
CLASSIFICATION : Maximum conductor temperature 90 °C
Circuit voltage not exceeding 33,000 volts
TESTING VOLTAGE : 17,000 volts
REFERENCE : ICEA S-66-524
  25 KV-CC

ALL ALUMINIUM SPACED AERIAL CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Compacted round
stranded hard drawn Aluminum
Conductors,Sizes. 35 mm2 up to 240 mm2
INSULATION :
Cross-linked polyethylene (XLPE) Color : Natural
SHEATH : Cross-linked polyethylene (XLPE) Color : Black
CLASSIFICATION : Maximum conductor temperature 90 °C
Circuit voltage not exceeding 25,000 volts
TESTING VOLTAGE : 38,000 volts
REFERENCE : ICEA S-66-524


  69 KV-CE (CU. WIRE SCREEN)

69 kV 90 °C CROSS-LINK POLYETHYLENE INSULATED WITH COPPER WIRE SCREEN POLYETHYLENE JACKETED POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single core
CONDUCTOR : Compact concentric
stranded uncoated annealed
Copper conductor
INSULATION :
Cross-linked polyethylene Color: Natural
SHEATHED : Polyethylene
TESTING VOLTAGE : 90,000 Volts
CLASSIFICATION : Maximum conductor temperature 90 °C
REFERENCE : IEC 60840: 1999
 35 KV-CC

ALL ALUMINIUM SPACED AERIAL CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single Core
CONDUCTOR : Compacted round
stranded hard drawn aluminum Conductors, Sizes 35 mm2 up to
240 mm2
INSULATION :
Cross-linked polyethylene (XLPE) Color : Natural
SHEATH : Cross-linked polyethylene (XLPE) Color : Black
CLASSIFICATION : Maximum conductor temperature 90 °C
Circuit voltage not exceeding 35,000 volts
TESTING VOLTAGE : 49,000 volts
REFERENCE : ICEA S-66-524

  18/30(36) KV-CV

18/30 kV 90 0 C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER
CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single and 3 cores
CONDUCTOR : Compact round stranded annealed copper,
Sizes. 35 mm2 up to 1,000 mm2
INSULATION :
Cross-linked polyethylene
Color : Natural (Translucent)
Core identification: Color tape White,
Red and Blue
SHEATHED : PVC Color : Black
SHIELD : Copper tape, thickness 0.1 mm
TESTING VOLTAGE : 63,000 Volts
CLASSIFICATION : Maximum conductor temperature 90 °C
REFERENCE : IEC 60502-2


  115 KV-CE (CU. WIRE SCREEN)

115 KV 90 °C CROSS-LINK POLYETHYLENE INSULATED WITH COPPER WIRE SCREEN AND POLYETHYLENE JACKETED POWER CABLE
CABLE STRUCTURE
NUMBER OF CORE :
Single core
CONDUCTOR : Compact concentric
stranded uncoated annealed
Copper conductor
INSULATION :
Cross-linked polyethylene Color: Natural
SHEATHED : Polyethylene
TESTING VOLTAGE : 160,000 Volts
CLASSIFICATION : Maximum conductor temperature 90 °C
REFERENCE : IEC 60840: 1999